Analysis of the Feasibility of Zinc Sleeve Layer Insulators on 150 kV Transmission Towers Based on Leakage Current

Authors

  • Ade Satria Universitas Islam Sultan Agung
  • Arief Marwanto Universitas Islam Sultan Agung

DOI:

https://doi.org/10.59061/jsit.v9i1.1452

Keywords:

Corrosion, Insulator, Leakage Current, The High Voltage Overhead Line System, Zin Sleeve

Abstract

The study addresses anomalies in insulator leakage current caused by corrosion, cracking, weather exposure, and salt spray pollution in coastal transmission lines. These issues were identified during the annual maintenance of the Sanur–Pesanggaran 150 kV transmission line at Tower 1 Pole 53. Additional contributing factors include the insulators’ service life of 25–30 years and inadequate cleaning maintenance. Such conditions increase the risk of flashover and insulator failure, reducing transmission system reliability. This research evaluates the feasibility of glass insulators equipped with a zinc sleeve layer to improve corrosion resistance, reduce leakage current, and extend service life in coastal environments. The methodology involved determining the insulator model, analyzing PLN inspection reports (2023), collecting installed insulator data, measuring leakage current, and assessing post-test conditions. The study examined 83 towers along the Pesanggaran–Sanur 1 transmission line. Results indicate that the insulator at Pole 53 failed to meet the required standard, whereas zinc sleeve-coated insulators on other poles complied with IEC 60815:2021 based on leakage current test results.

References

Alam, A. S., Syakur, A., & Supriyadi, G. (n.d.). Studi fenomena arching discharge pada isolator dengan kondisi lingkungan berpolutan berat. Transmisi: Jurnal Ilmiah Teknik Elektro, 26(1), 17–23. https://doi.org/10.14710/transmisi.26.1.17-23

Ambabunga, Y. M., & Masiku, H. (2023). Analisis kerusakan isolator saluran transmisi tegangan tinggi akibat pengaruh polutan (kondisi kering dan basah). Universitas Kristen Indonesia Toraja. https://doi.org/10.47178/dynamicsaint.v6i2.1369

Budiman, T. W. (2019). Audit energi listrik dan analisis peluang penghematan konsumsi energi listrik pada sistem pendingin dan pencahayaan di Gedung D3 Ekonomi UII.

David, F., & Nazir, R. (2005). Analisa arus bocor pada isolator suspension tipe ball & socket saluran transmisi 150 kV akibat pengotoran uap garam dan debu semen.

Direksi PT PLN (Persero). (2014). Buku pedoman pemeliharaan saluran udara tegangan tinggi dan tegangan ekstra tinggi. PT PLN (Persero).

Haryanty, E. (2022). Pemeliharaan isolator pada saluran udara tegangan tinggi PT PLN (Persero) UPT Probolinggo.

Joto, R., Kharisma, D. D., Syamsuri, T. U., & Imron, A. (2023). Pengaruh efek kontaminasi isolator keramik terhadap rugi daya saluran udara tegangan tinggi. ELPOSYS: Jurnal Sistem Kelistrikan, 10(3), 167–171. https://doi.org/10.33795/elposys.v10i3.4222

Kumagai, K., Minami, K., Sugai, Y., Sumiyoshi, T., & Komaru, T. (2019). Effect of ablation at high-dominant frequency sites overlapping with low-voltage areas after pulmonary vein isolation of nonparoxysmal atrial fibrillation. Journal of Cardiovascular Electrophysiology, 30(10), 1850–1859. https://doi.org/10.1111/jce.14090

Marjerrison, M. (1968). Electric transmission tower design. Journal of the Power Division, 94(1), 1–23. https://doi.org/10.1061/JPWEAM.0000575

Mayangsari, D. F., Adianto, H., & Yuniati, Y. (2015). Usulan pengendalian kualitas produk isolator dengan metode failure mode and effect analysis (FMEA) dan fault tree analysis (FTA). Reka Integra, 3(2).

Naimi, R. (2019). Penggantian temuan isolator korosi pada line Asam-Asam arah Cempaka.

Patel, D., Pandey, G., Mourya, V. K., & Kumar, R. (2024). Sustainable base isolation: A review of techniques, implementation, and extreme events. Sadhana, 49(2), Article 173. https://doi.org/10.1007/s12046-024-02511-1

PLN UPT Bali. (2023). Hasil asesmen kondisi isolator pada SUTT sekitar Pantai UPT Bali.

Punse, G. S. (2014). Analysis and design of transmission tower. International Journal of Modern Engineering Research, 4(1), 116–138.

Warmi, Y., & Febrian, K. (2021). Analisis variasi ketebalan coating senyawa glasir terhadap daya tahan dielektrik isolator keramik saluran transmisi 150 kV. ELKOMIKA: Jurnal Teknik Energi Elektrik, Teknik Telekomunikasi, dan Teknik Elektronika, 9(2), 249. https://doi.org/10.26760/elkomika.v9i2.249

Downloads

Published

2026-06-26

How to Cite

Ade Satria, & Arief Marwanto. (2026). Analysis of the Feasibility of Zinc Sleeve Layer Insulators on 150 kV Transmission Towers Based on Leakage Current. Jurnal Sains Dan Ilmu Terapan, 9(1), 338–349. https://doi.org/10.59061/jsit.v9i1.1452

Similar Articles

1 2 3 4 5 6 > >> 

You may also start an advanced similarity search for this article.