Analisis Susut Energi Listrik pada Trafo Distribusi 160 KVA di Gardu Distribusi SP022 PLN ULP Sape Penyulang Sari Akibat Ketidakseimbangan Beban
DOI:
https://doi.org/10.59061/jentik.v3i1.950Keywords:
Distribution Transformer, Load Imbalance, Power Losses, SP022 SubstationAbstract
This research aims to analyze the operational conditions of distribution transformers at the SP022 PLN ULP Sape substation, with a focus on calculating load imbalances caused by transformer losses. The data collected includes voltage and current measurements, as well as calculation analysis related to energy losses. The analysis results show that there is a significant load imbalance. Current measurement data shows that the load imbalance during the day is 9.967%, while at night it increases to 12.63%. The total transformer loss was recorded at 526,041 W during the day and 770,359 W at night. The energy losses that occur respectively are 15,556 kWh/day with an estimated loss cost of IDR 22,473.7 per day or 466,704 kWh per month with a loss cost of IDR 674,247.26 per month. The results of this research show that although losses due to imbalance are still within tolerance limits, regular repairs can reduce power losses and operational costs, thereby increasing the efficiency of distribution transformers.
References
Avif, M., Andriawan, A. H., & Prenata, G. D. (2022). Analisis pembebanan transformator daya 300 KVA di instalasi pengolahan air limbah PT. SIER.
Deeng, A. S., Mangindaan, G. M. C., & Patras, L. S. (2022). Studi kelayakan operasi perencanaan uprating SUTM pada penyulang SK 2 & SK 4 di gardu induk Kawangkoan dengan metode simulasi ETAP 12.6.0.
Ginting, R. T. (2022). Analisis ketidakseimbangan beban jaringan distribusi tegangan rendah menggunakan ETAP. Jurnal Sain, Energi, Teknologi & Industri, 6(2), 81–89. https://doi.org/10.31849/sainetin.v6i2.9734
Latupeirissa, H. L., & Titaley, G. V. (2023). Analysis of the effect of load imbalance on neutral current and power losses in distribution transformer. Journal Name, 3(4).
Osahenvemwen, O. A., & Okhumeode. (2020). The effects of unbalanced load in power distribution sub-station network. Journal Name, 3(5), 1–11. Retrieved from www.iarjournals.com
Rachman, A. Y. D., Teknik Elektro, D., & Teknik Elektro, M. (2012). Perencanaan saluran udara tegangan menengah (SUTM) 20 kV pada komplek perkebunan AMP (Agra Masang Perkasa) Bawan Lubuk Basung. Retrieved from http://www.novapdf.com/
Ridwan, M., Ridal, Y., & Rauf, R. (2024). Analisa pengaruh pemeliharaan preventif pada penyulang gasan di PT. PLN (Persero) ULP Pariaman. E-Mail Teknik Jurnal, 4, 33–37.
Rohmat, K., & Riyadi, M. (2023). Analisis ketidakseimbangan beban transformator distribusi di PT. PLN (Persero) UPDL Pandaan. Transmisi: Jurnal Ilmiah Teknik Elektro, 25(4), 186–192. https://doi.org/10.14710/transmisi.25.4.186-192
Soedjarwanto, N., Kines, K. E., & Aulia, S. A. (2024). Analisis susut daya (losses) pada penyulang Rayap PT PLN (Persero) UID Lampung berbasis aplikasi ETAP 19.0.1. Jurnal Informatika dan Teknik Elektro Terapan, 12(2). https://doi.org/10.23960/jitet.v12i2.4072
Trunojoyo, J., Blok M-K., Baru, K., & Direksi, L. K. (n.d.). Power quality (regulasi harmonisa, flicker dan ketidakseimbangan tegangan) PT PLN (Persero).
Wirawan, A. D., Junaidi, & Arsyad, M. I. (2021). Analisa pengaruh ketidakseimbangan beban terhadap arus netral dan losses pada transformator distribusi di penyulang Pangsumah PT. PLN (Persero) Rayon Mempawah.
Downloads
Published
How to Cite
Issue
Section
License
Copyright (c) 2024 Jurnal Elektronika dan Teknik Informatika Terapan ( JENTIK )

This work is licensed under a Creative Commons Attribution-NonCommercial-ShareAlike 4.0 International License.